Walgreens No. 17169
November 18, 2022 · Fail
🪳cooked
- official resultFail
- resultFail
- inspection typeRetail Food
- failed findings9
- critical findings2
Failed findings
-
Safe Unadulterated and Honestly Presented (P)criticalInspector note: TCS foods without the benefit of mechanical refrigeration for 24 hours have been removed from service and are in bags in back room. To be Denatured and discarded when trash company arrives on site per PIC. All liquid perishables (milk) have already been discarded into service sink. Provide list of foods discarded and final disposition from trash company.
-
System Maintained in Good Repair (P)criticalInspector note: Plumber on site snaking drain with toilet removed from restroom and replacing fixtures at the time of inspection. Apply for plumbing permit @ 1010 Massachusetts Ave 5th floor plumbing division. Toilet tank is cracked and has been glued. Repair/replace.
-
Prohibiting Animals (Pf)Inspector note: Dog observed in store. Service animals only. Handout provided.
-
(A) Ceasing Operations and Reporting (Pf)Inspector note: Toilet overflowed in back room on morning of 11/17/22 and leaked onto basement electrical and fire panel. BFD cut power to establishment. Establishment was without power for 24 hours. PIC shall report to ISD health whenever imminent health hazard exists. (power loss watewater backup). Power has since been restored.
-
Nonfood Contact Surfaces (C)Inspector note: Employee restroom toilet in back room backed up morning of 11/17/22 and leaked non potable water into basment. Clean and disinfect all affected areas. Provide invoice from a proffessional cleaning company upon reinspection.
-
Frequency-Removal (C)Inspector note: Both carboard of refuse dumpster brimming with refuse. Increase pickups as needed. Ensure Site cleanliness permit on record link provided via email.
-
Floors Walls and Ceilings-Cleanability (C)Inspector note: Floor in foyer with missing covering. Laminate floor in some areas of retail sales floor missing or damaged. Repair.
-
Repairing-Premises Structures Attachments and Fixtures-Methods (C)Inspector note: Electrical panel and fire alarm panel were exposed to water from toilet backup on 11/17/22. Make all necessary repairs and apply for all applicable permits with ISD. Provide documentation of alarm panel reset for life safety and that fire alarm is operating per applicable codes.
-
Cleaning of Plumbing Fixtures (C)Inspector note: Clean and disinfect restroom where backup occured.
What changed since the previous inspection?
Compared with Fail on July 21, 2022: 8 findings appeared for the first time. 1 finding recurred. 2 previous findings did not recur.